Burkert > Type 8045


Burkert : Type 8045 - Insertion magnetic inductive flowmeter


   Type 8045 - The electromagnetic flowmeter 8045 is made up of an electronic module including a backlit display, operating keys and a sensor consisting of PVDF or stainless steel material. It has been designed to measure a flow rate of neutral and slightly aggressive fluids with a conductivity of more than 20 µS/cm in DN06...DN400 pipes. It is equipped with a 4...20 mA output, a digital output (pulse output by default). Some versions are equipped with two relay outputs and one digital input. Two independent totalizers allow counting the flow rate. The available process connections are: - G2” connection for the version with a PVDF sensor - G2” or clamp connection for the version with a stainless steel sensor. The version with a stainless steel sensor can be used in applications with higher pressures (PN16) and higher temperatures (110°C). The version with Alloy C22 electrodes has been designed for applications with aggressive fluids (chemicals) and especially sea water applications.

   Description Burkert Type 8045 - Insertion magnetic inductive flowmeter

■ Sensor without moving parts
■ Indicates both flow rate and volume
■ Simulation of all output signals
■ Clean in place (CIP), FDA-compliant materials
■ Version with Alloy C22 electrodes